Specifications
A6 975-0125-02-01
Invert Power Derating vs Ambient Temperature
The inverter/charger delivers up to 2000 watts continuous of sine wave output to
50 °C ambient temperature and 1500 watts continuous of sine wave output to 60
°C ambient temperature, derated linearly from 50 °C to 60 °C.
If the unit is in elevated ambient temperature above 50 °C, you are required to
reduce power draw according to the Figure A-1 to avoid over-temperature
shutdown.
Charger Mode
Total maximum charger output is 100 amps DC to 60 °C ambient. In higher
ambients, the main charger will automatically derate (reduce output current) to
maintain internal temperatures at a safe level.
Figure A-1
Inverter Output Power vs Ambient Temperature
-20
500
1000
1500
2000
-10 0 10 20 30 40 50 60
Ambient Temperature (°C )